
- Inside contamination 0 %
- Outside contamination 0 %
- Filling 0 %
- Spray losses including drift 0 %
- Remnants 0 %
- Evaluation results 0 %
Internal cleaning of complete sprayer in the field
- Rinse tank
{{rinsetank1.jpg}} {{rinsetank2.jpg}} {{rinsetank3.jpg}}
- No rinse tank present
- Undersized (not sufficient for complete internal cleaning in the field)
- Standard capacity
==== Reference Standards ==== **ISO 4254-6; ISO 13440** ==== Performance criteria ==== A water tank for rinsing the spraying equipment shall be provided. This tank shall not be combined with the clean water tank for the operator`s use (see 4.11 of EN 907:1997). It shall have a volume of at least 10 % of the nominal tank volume or at least 10 times the volume of residual which can be diluted (see 2.2 of ISO 13440:1996). In the latter case, the volume of residual of tank shall be specified in the instruction handbook.
- Oversized 20% above standard (to allow internal and external cleaning in the field)
- Cleaning system
==== Reference Standards ==== **EN 12761-3** ==== Performance criteria ==== Water tanks shall be designed so that they can be connected with the equipment in such a way that the rinsing of the pipes is possible even when the tank is filled to its nominal volume. In addition, the dilution of the volume of residual in the tank shall be possible.
>> Shunt device (system of two 3 way valves enabling to rinse separately the main tank and the sprayer hydraulic circuit){{O-11.jpg}}
- Not available
- Available
{{F-9.jpg}}
- Cleaning system
==== Reference Standards ==== **EN 12761-3** ==== Performance criteria ==== Water tanks shall be designed so that they can be connected with the equipment in such a way that the rinsing of the pipes is possible even when the tank is filled to its nominal volume. In addition, the dilution of the volume of residual in the tank shall be possible.
>> Rinse water induction- No rinse water available
- Take over the rinsing water by gravity without rinse nozzles, manually controlled
- Take over the rinsing water by gravity without rinse nozzles, remote controlled
- Uptake the rinsing water by the pump using a 3 way valve, without rinse nozzles, manually controlled
- Uptake the rinsing water by the pump using a 3 way valve, with rinse nozzles, manually controlled
- Uptake the rinsing water by the pump using a 3 way valve, remote control for automatic dilution of the spray residues in the bottom of the tank (tank residual volumes). No control of the volume of clean water used
- Uptake over the rinsing water by the pump using a 3 way valve, remote control for automatic dilution of the spray residues in the bottom of the tank (tank residual volumes). Control of the volume of clean water used
- Stepwise cleaning system
{{stepwise_rinsing.jpg}}
- Continouos cleaning system using a separate pump
{{continuous_cleaning.jpg}}
- Cleaning system
==== Reference Standards ==== **EN 12761-3** ==== Performance criteria ==== Water tanks shall be designed so that they can be connected with the equipment in such a way that the rinsing of the pipes is possible even when the tank is filled to its nominal volume. In addition, the dilution of the volume of residual in the tank shall be possible.
>> Rinse nozzle management{{rinse_nozzle1.jpg}} {{rinse_nozzle2.jpg}}
- No rinse nozzle available
- No rinse nozzle available, use of spray lance
{{spray_lance.jpg}}
- Rinse nozzles
- Spray tank
>> Design
- Tank with irregular shape, dead areas and angles
{{irregular_shape_tank.jpg}}
- Tank with partly irregular shape
{{O-37.jpg}}
- Tank with regular shape
{{regular_tank_shape1.jpg}}
- Tank with irregular shape, dead areas and angles
- Spray tank
>> Inside surface
==== Reference Standards ==== **EN 12761-3, 4.1.1.1; ISO 4287; ISO 4288** ==== Performance criteria ==== Depth of roughness of inner and outer walls of the tank shall be such that Rz <= 100 µm as specified in ISO 4287, and measured according to ISO 4288. {{roughness.jpg}}
- Rough, coarsness can be felt on surface
- Smooth, no coarsness can be felt on surface
- Rinse nozzle
>> Type
- Not available
- Nozzle with low energy, normally used for cleaning of cans
{{O-48.jpg}}
- Nozzle with high energy of water jet
{{O-49.jpg}}
- Rotating axle along the tank equipped with nozzles
{{damann_scheme.jpg}}
- Rinse nozzle
>> Position
- Nozzle(s) cannot reach all areas of the tank
{{rinse_nozzle2.jpg}}
- Nozzle(s) can reach all areas of the tank
{{rinse_nozzle_position.jpg}}
- Nozzle(s) cannot reach all areas of the tank
Cleaning of concentrated PPP
- Cleaning of PPP cans
>> Device
==== Reference Standards ==== **EN 12761-3, clause 7 ISO 21278-2, clause 5.8** ==== Performance criteria ==== Devices for cleaning crop protection product cans, when provided, shall be designed so that the volume of residue after cleaning is less than 0,01 % of the nominal can volume.
- No rinsing nozzle for cans
- Rinsing nozzle for cans located in strainer
{{can_rinse_nozzle.jpg}}
- Induction hoppers with rinsing nozzle for cans
{{O-69.jpg}} {{hopper2.jpg}}
- Cleaning of PPP cans
>> Operation
==== Reference Standards ==== **EN 12761-3, clause 7 ISO 21278-2, clause 5.8** ==== Performance criteria ==== Devices for cleaning crop protection product cans, when provided, shall be designed so that the volume of residue after cleaning is less than 0,01 % of the nominal can volume.
- Shut-off valve operated by pushing down by the can
{{O-69.jpg}}
- Separate hand operated valve
{{hand_operated_valve.jpg}}
- Shut-off valve operated by pushing down by the can
- Cleaning of PPP cans
>> Size
- Size not allowing cleaning of 20 l cans
- Size allowing cleaning of 20 l cans
Homogeneous spray liquid
- Agitation system
==== Reference Standards ==== **EN 12761-3, clause 4.1.1.5 ISO 5682-2** ==== Performance criteria ==== Tanks shall be equipped with devices (e.g. agitators) to ensure an even concentration of mixture. The maximum allowable deviation is 15 % when tested in accordance with ISO 5682-2.
- No agitation system (just backflow)
- Poor agitation /residues on bottom of tank
{{O-77.jpg}}
- Agitation visually effective and no residues on tank bottom
{{agitation.jpg}}
- Agitation at standard
{{agitation_graphs_standard.jpg}}
- Agitation above standard
{{agitation_graphs_above_standard.jpg}}
- Agitation intensity adjustment (regulation of agitation flow rate)
- No intensity adjustment
- Manual intensity adjustment
{{agitation_manually.jpg}}
- Remote controlled intensity adjustment
- Automatic intensity adjustment (sensor+computer)
{{agitation_automatic.jpg}}
Cleaning filters
- Type and position of suction filters
==== Reference Standards ==== **EN 12761-3, clause 4.1.3** ==== Performance criteria ==== Sprayers equipped with a positive displacement pump shall have a suction filter. On the pressure side, the liquid going to the nozzles shall be filtered by means of central filters or filters in the lines of spraying sections. The mesh size of filters shall correspond to the size of nozzles fitted on the sprayer. This applies also to nozzle and pump filters. {{filtering_scheme.jpg}}
- No filter
- If opened loss of liquid
==== Reference Standard ==== **EN 12761-3** ==== Performance criteria ==== It shall be possible, with the tank filled to ist nominal volume, to clean central filters without any spray liquid leaking out except for that which may be present in the filter casing and suction or pressure lines. {{F-82.jpg}}
- Filter with drainable valve
{{agitation_manually.jpg}}
- Filter without loss of liquid when opened
{{O-90.jpg}}
- Type and position of filters in pressure line
==== Reference Standards ==== **EN 12761-3, clause 4.1.3** ==== Performance criteria ==== Blockages shall be indicated to the driver, for example by an appropriate positioning of the central pressure filters and pressure gauge. Filters shall be easily accessible and filter insets shall be removeable. For quick cleaning the filter tissue of the inset shall be easily accessible. It shall be possible, with the tank filled to its nominal volume, to clean central filters without any spray liquid leaking out except for that which may be present in the filter casing and suction or pressure lines.
- No filter
- If opened loss of liquid
{{filter_spray_loss.jpg}}
- Filter with drainable valve
- Filter without loss of liquid when opened
{{filter_no_spray_loss.jpg}}
- Selfcleaning
{{self_cleaning.jpg}}
- Liquid filtration system
==== Reference Standards ==== **EN 12761-3, clause 4.1.3** ==== Performance criteria ==== Blockages shall be indicated to the driver, for example by an appropriate positioning of the central pressure filters and pressure gauge. Filters shall be easily accessible and filter insets shall be removeable. For quick cleaning the filter tissue of the inset shall be easily accessible. It shall be possible, with the tank filled to its nominal volume, to clean central filters without any spray liquid leaking out except for that which may be present in the filter casing and suction or pressure lines.
- No filter
- suction filters and pressure filters and section filters and nozzle filters
- suction filters and pressure filters and nozzle filters
- suction filters and pressure filters and section filters
- one suction filter an two section filters
- 1 suction filter and 1 pressure filter
EOS = Environmentally Optimised Sprayer
Evaluates technologies of Crop Protection sprayers on their risk mitigation capabilities to protect water and the environment
Top menu bar indicates relavant evaluation areas – click: if green it is active- Click on „problem“ menu bar below to open evaluation questionaire
- Technologies are listed in blue
- Click on one technical solution between each of the blue headlines (click on question marks to see an explaination (picture / comment)
- Go through the questionaire and complete all 5 areas indicated on top bar (after the completion of one area: click next button or next problem menu bar
- Technical solutions selected are compared with best available option by the EOS index (best is 100%). Results are shown by clicking on Evaluation results or in the buttons of the evaluation areas
- Results can be saved by clicking on save symbol: Enter a name and the E-Mail
Preventing external contamination
- Fan design
- Air inlet nearby next to the nozzles
{{axial_fan_inlet_close_to_nozzle.jpg}}
- Air inlet behind the nozzles
{{O-107.jpg}}
- Air inlet before the nozzles
{{air_inlet_before_the_nozzle.jpg}}
- Air inlet nearby next to the nozzles
- Spray tank outside surface
- Rough, coarsness can be felt on surface
- Smooth, no coarsness can be felt on surface
- Cover on components
- Not available
{{O-110.jpg}}
- Partly covered (<50%)
- Covered
{{O-112.jpg}}
- Not available
External cleaning of complete sprayer in field
- Cleaning device
>> Type
- Not available
- Brush
{{O-115.jpg}}
- Lance
{{O-116.jpg}}
- Spray gun up to 8 bar
{{spray_gun.jpg}}
- Medium pressure spray gun (> 8 bar to 50 bar)
{{medium_pressure_spray_gun.jpg}}
- High pressure cleaner (> 50 bar)
{{high_pressure_cleaner.jpg}}
- Cleaning device
>> Exposure to contamination
- Not protected from direct contamination while spraying
{{O-122.jpg}}
- Protected from direct contamination while spraying (covered)
{{O-123.jpg}}
- Not protected from direct contamination while spraying
- Cleaning device
>> Supply system
- No separate pump and lines for cleraning process
- Separate pump and lines for cleaning process
- Rinse water capacity (volume meant for external cleaning)
- Not available
- up to 10 litres
- from 10 to 20 litres
- more than 20 litres
EOS = Environmentally Optimised Sprayer
Evaluates technologies of Crop Protection sprayers on their risk mitigation capabilities to protect water and the environment
Top menu bar indicates relavant evaluation areas – click: if green it is active- Click on „problem“ menu bar below to open evaluation questionaire
- Technologies are listed in blue
- Click on one technical solution between each of the blue headlines (click on question marks to see an explaination (picture / comment)
- Go through the questionaire and complete all 5 areas indicated on top bar (after the completion of one area: click next button or next problem menu bar
- Technical solutions selected are compared with best available option by the EOS index (best is 100%). Results are shown by clicking on Evaluation results or in the buttons of the evaluation areas
- Results can be saved by clicking on save symbol: Enter a name and the E-Mail
Spill protection during PPP induction
==== Reference Standards ====
**ISO 4254-6 5.4.2 **
==== Performance criteria ====
To limit the risk of exposure to chemicals during filling/cleaning operations:
- a chemical induction bowl or equally effective device shall be provided with the sprayer;
- alternatively, the filling hole of the spray tank shall be so positioned that the height from the ground or platform is not more than 1 300 mm, with the horizontal reach between the rim of the hole and the outer edge of any part of the sprayer which could hinder the operator being not be more than 300 mm at the operator filling position (see Figure 1).
{{filling_hole_position.jpg}}
- Powder mixer in strainer
- Not available
- with no container cleaner
{{mixer_no_cleaner.jpg}}
- with container cleaner in separate strainer
{{can_clean_separate.jpg}}
- combined with container cleaner
{{mixer_with_cleaner.jpg}}
- Injector with sucking tube
{{O-143.jpg}}
- Not available
- on the tank top wall
{{injector_tank_top.jpg}}
- on the tank lid
{{injector_tank_lid.jpg}}
Water induction
- Filling hole
>> Diameter
==== Reference Standards ==== **EN 12761-3 4.1.1.2 ISO 9357 Table 1** ==== Performance criteria ==== The filling hole minimum diameter shall correspond to the nominal tank volume as below:
Nom. tank vol. ø of filling hole <100 l 100 mm 100 -150 l 150 mm 200 - 600 l 200 mm > 600 l 300 mm - less than the standard
- according to the standard
- greater than the standard
- Filling hole
>> Position
==== Reference Standards ==== **ISO 4254-6 5.4.2** ==== Performance criteria ==== The filling hole of the spray tank shall be so positioned that the height from ground or platform is not more than 1300 mm, with the horizontal reach between the rim of the hole and the outer edge of any part of the sprayer which could hinder the operator being not be more than 300 mm at the operator filling position. {{filling_hole_position.jpg}}
- less accessible than the standard
- according to the standard
- better accessible than the standard
- Filling hole
>> Strainer depth
==== Reference Standards ==== **EN 12761-3 4.1.1.2** ==== Performance criteria ==== The minimum depth of the strainer shall correspond to the nomional tank volume as below:
Nom. tank vol. Depth of strainer up to 150 60 mm from >150 to 400 100 mm from >400 to 600 150 mm > 600 250 mm - strainer depth less than standard
- strainer depth according to standard
- strainer depth greater than standard
- Filling device
>> Type
==== Reference Standards ==== **EN 12761-3 4.1.1.2** ==== Performance criteria ==== The filling device should be designed so that the liquid is prevented from the back-flow from the tank to the water supply system
- Not available
- With no back-flow protection
- With back-flow protection
{{filling_device_orchard.jpg}}
- Filling device
>> Exposure to contamination
- Exposed when not in use
{{filling_device_exposed.jpg}}
- in a covered compartment when not in use
- Exposed when not in use
Overflow protection
- Tank overvolume
==== Reference Standards ==== **ISO 4254-6 5.4.2 EN 12761-3 4.1.1.2** ==== Performance criteria ==== The actual overall volume of the tank shall exceed the nominal volume by at least 5 %. {{overvolume_scheme.jpg}}
- No tank overvolume
- 5% of nominal tank volume
- 10% of nominal tank volume
- Liquid level indicator
>> Type
==== Reference Standards ==== **ISO 4254-6 5.4.2 EN 12761-3 4.1.1.4 ISO 9357 Table1** ==== Performance criteria ==== The nominal volume of the tank shall be marked. The acceptable tolerances of the contents indicator are: a) 7,5 % for each graduation mark for volumes up to 20 % of the nominal tank volume; b) 5 % for each graduation mark for volumes above 20 % of the nominal tank volume. Explanation: The tolerances shall be measured with a maximum error on measurement of 1 % with the sprayer in a horizontal position.
- Not available
- direct
{{O-173.jpg}}
- wet tube
{{O-174.jpg}}
- dry tube
{{dry_tube.jpg}}
- float-and-clock
{{O-176.jpg}}
- electronic level gauge
{{electronic_level_gauge.jpg}}
- Liquid level indicator
>> Scale interval
==== Reference Standards ==== **EN 12761-3 4.1.1.4 ISO 9357 Table 1** ==== Performance criteria ==== Scaling according to the standard:
Nominal tank capacity Scale <100 l 1 l 100 - 150 l 25 l 200 -1000 l 50 l >1000 l 100 l - greater than the standard
- according to the standard
- less than the standard
- Liquid level indicator
>> Visibility
==== Reference Standards ==== **EN 12761-3 4.1.1.4** ==== Performance criteria ==== The liquid level indicator should always be well seen from the operator's seat and from the place from where the sprayer is filled
- neither visible from the tractor cabin nor from the filling place
- visible only from the tractor cabin
- visible only from the filling place
- visible both from the trcator cabin and the filling place
- Measuring flow of water
- not available
- flow monitoring & manual shut-off
- programmable flowmeter & automatic shut-off
{{O-190.jpg}}
- Sensing the level of liquid in tank
- not available
- electronic level gauge - tank-full alarm
{{tank_full_alarm.jpg}}
- electronic level gauge - automatic shut-off
{{electronic_level_gauge.jpg}}
- external inductive level sensor - tank-full alarm
- external inductive level sensor - automatic shut-off
Overpressure protection in tank
- Pressure compensation in tank
==== Reference Standards ==== **ISO 4254-6 5.4.2** ==== Performance criteria ==== A pressure-compensation device shall be fitted on tanks that are not designed to be put under pressure, in order to keep them at atmospheric pressure when emptying and filling.
- not available
- pressure compensation device (e.g. air valve)
{{pressure_compensation.jpg}} {{pressure_compensation_scheme.jpg}}
Enabling filling in field
- Transport of PPPs
- No PPP locker available for transport in the field
- lockable PPP locker retaining spills
{{lockable_ppp_locker.jpg}}
- unlockable PPP locker retaining spills
Enabling dosing in field
- PPP dose measuring devices
>> transport
- no locker for measuring jar or weighing device
- locker for measuring jar or weighing device
{{O-209.jpg}}
- PPP dose measuring devices
>> cleaning
- no cleaning facilities for measuring devices
- cleaning facilities for measuring devices (e.g. container cleaner)
{{measuring_device_cleaner.jpg}}
- PPP dose measuring devices
>> measuring place
- no dedicated, horizontal working surface retaining spils
- dedicated, horizontal working surface retaining spils
{{O-215.jpg}}
EOS = Environmentally Optimised Sprayer
Evaluates technologies of Crop Protection sprayers on their risk mitigation capabilities to protect water and the environment
Top menu bar indicates relavant evaluation areas – click: if green it is active- Click on „problem“ menu bar below to open evaluation questionaire
- Technologies are listed in blue
- Click on one technical solution between each of the blue headlines (click on question marks to see an explaination (picture / comment)
- Go through the questionaire and complete all 5 areas indicated on top bar (after the completion of one area: click next button or next problem menu bar
- Technical solutions selected are compared with best available option by the EOS index (best is 100%). Results are shown by clicking on Evaluation results or in the buttons of the evaluation areas
- Results can be saved by clicking on save symbol: Enter a name and the E-Mail
Sprayer configuration
- Shape of the boom and nozzle position with respect to target
- Canon sprayer
{{canon_sprayer.jpg}}
- semi circular boom along the axial fan
{{semi_circular_boom.jpg}}
- vertical boom with fixed nozzle positions (e.g tower shaped air-assisted sprayer)
{{vertical_boom.jpg}}
- vertical boom with adjustable nozzle positions (e.g 'Oktopus' sprayer)
{{O-283.jpg}}
- multi-row sprayer with spouts/nozzles on top of the sprayer body
{{spout_top.jpg}}
- multi-row sprayer with spouts/nozzles mounted on supports for each row allowing side by side spraying
{{O-285.jpg}}
- not shielded recycling sprayer
{{O-286.jpg}}
- shielded tunnel sprayer
{{O-287.jpg}}
- shielded tunnel sprayer with recycling system
{{tunnel_with_recycling.jpg}}
- Canon sprayer
Droplet size adjustment
Drift risks are very much related to the level of pulverization of liquid: droplets smaller than 100 µm are more prone to drift and it is important that during the application the fraction of very fine droplets is contained as much as possible. There are essentially two ways through which act in order to adjust the droplet size: the modification of the operating pressure (but this implies a consequent variation in the nozzles flow rate and therefore on the volume rate applied) or the change of nozzle.
- Pressure adjustment
- Not available
- manual
- automatic adjustment
- Nozzle change
- manual by desmounting
- manual multiple nozzle holder
{{multiple_nozzle_holder.jpg}}
- automatic
Application precision
- Target identification system
- Not available
- GPS/GIS
- Optical/infrared
{{ultrasonic_sensor_orchard.jpg}}
- GPS + optical/infrared
- Section control
==== Reference Standards ==== **EN 12761-3, clause 4.1.8** ==== Performance criteria ==== It shall be possible to switch off the spray of each side of the sprayer independently.
- manual
{{section_manual_control.jpg}}
- electrical
{{section_electric_control.jpg}}
- GPS/GIS based
- manual
Air flow adjustment
- Air flow volume
==== Reference Standards ==== **EN 12761-3, clause 4.1.8** ==== Performance criteria ==== It shall be possible to switch off the blower(s) independently from other driven parts of the machine.
- Not available
- gear box
- hydraulic
- fan blades angling
{{fan_blades_angling.jpg}}
- Gear box + fan blades angling
- Air flow distribution
- Not available
- Shields for manual closing the air outlet on side of the sprayer
{{O-305.jpg}}
- Shields for automatic closing the air outlet on side of the sprayer
- Remote controlled shields for closing the air outlet on side of the sprayer
- Independant adjustment of air flowrate on the left and on the right side of the sprayer
{{independant_air_side_adjustment.jpg}}
- Air flow direction
==== Reference Standards ==== **EN 12761-3, clause 4.1.8** ==== Performance criteria ==== It shall be possible for one person to adjust the liquid and air-jets according to the respective crop type and height in a reproducible way, by appropriate means such as marking, locking systems or patterns
- Not available
- manual
{{deflector_manual.jpg}}
- automatic
- remote controlled
Operational leakage protection
- Antidrip device
==== Reference Standards ==== **EN 12761-3, clause 4.1.4 EN 13790-2 clause 4.8.3** ==== Performance criteria ==== EN 12761-3: When the spraying stop control has been activated, the dripping shall not exceed 2 ml per nozzle during 5 min. The measuring is started 8 s after the flow has been shut off. EN 13790-2: After being switched off, the nozzles shall not drip. 5 s after the spray jet has collapsed there shall be no dripping.
- Not available
- enabling to stop dripping in more than 10 seconds
- enabling to stop dripping within 10 seconds
- enabling to stop dripping within 5 seconds
- enabling to stop dripping within 2 seconds
- Tank lid
==== Reference Standards ==== **EN 12761-3 ISO 4254-6 5.4.2** ==== Performance criteria ==== The lid shall be: - attached to the machine, e.g. by means of a chain; - fitted with a holding device ensuring a closed position either by means of a positive mechanical action or lids fixed by screwing; - fitted so as to prevent leakage of the spray mixture, e.g. by means of a seal.
- tight tank lid(s)
{{tight_tank_lid.jpg}}
- untight tank lid(s)
{{untight_tank_lid.jpg}}
- tight tank lid(s)
EOS = Environmentally Optimised Sprayer
Evaluates technologies of Crop Protection sprayers on their risk mitigation capabilities to protect water and the environment
Top menu bar indicates relavant evaluation areas – click: if green it is active- Click on „problem“ menu bar below to open evaluation questionaire
- Technologies are listed in blue
- Click on one technical solution between each of the blue headlines (click on question marks to see an explaination (picture / comment)
- Go through the questionaire and complete all 5 areas indicated on top bar (after the completion of one area: click next button or next problem menu bar
- Technical solutions selected are compared with best available option by the EOS index (best is 100%). Results are shown by clicking on Evaluation results or in the buttons of the evaluation areas
- Results can be saved by clicking on save symbol: Enter a name and the E-Mail
Application control
- Liquid flow adjustment
==== Reference Standards ==== **EN 12761-3, clause 4.2** ==== Performance criteria ==== Pressure adjustment devices shall maintain a constant working pressure at constant revolutions of the pump
- manual pressure regulator
{{manual_pressure_regulator.jpg}}
- DPA electronic
{{dpa.jpg}}
- manual pressure regulator
- Forward speed monitoring
- Not available
- engine RPM
- proximity/encoder sensors
{{proximity_sensors.jpg}}
- photocamera / radar
- GPS
- ON/OFF valve
==== Reference Standards ==== **EN 12761-3, clause 4.1.8** ==== Performance criteria ==== It shall be possible to switch off the spray of each side of the sprayer independently.
- manual
- electrical
- electronic (GIS/GPS based)
Dead volume protection
To minimise the amount of the not dilutable volume (indicated also as dead volume) in a sprayer is useful in order to limit risks of environmental pollution at the end of the application. The dead volume, according to standard ISO 13440:1996, clause 2.3 is the “part of the total residual volume “ that cannot flow back to the tank during normal operation of the sprayerâ€. It is mainly the volume of liquid that remains in the delivery hoses between the pump and the nozzles.
- Shape of filter / nozzle supply / safety valve
- No flush valves for draining dead volumes
- Flush valves for draining dead volumes
{{flush_valve.jpg}}
- Draining capability
==== Reference Standards ==== **ISO 4254-6** ==== Performance criteria ==== An emptying device in accordance with 4.5.3 of EN 907:1997 shall allow the complete emptying of the residual in the tank when the sprayer is in a horizontal position. Complete emptying of the residual is achieved if there are no visible puddles at the bottom of the tank after 5 min drainage.
- Complete draining of the tank not possible
{{complete_draining_not_possible.jpg}}
- Complete draining of the tank possible
- Complete draining of the tank not possible
Residual volume (drainable)
comment from Hans!!!
- Agitation shut-off
{{agitation_shut_off_scheme.jpg}}
- Not available
- Manual controlled agitation shut-off
{{manual_agitation_shut_off.jpg}}
- Remote-controlled agitation shut-off
- Automatic agitation shut-off
- Sump design
{{sump_design_scheme.jpg}}
- Not available
- Sump at the bottom of the main tank
{{O-263.jpg}}
- Return valve
{{return_valve_scheme.jpg}}
- Not present
- Present
{{O-266.jpg}}
- Other connections
- Not available
- Loss of liquid when the valve is opened
- No loss of liquid when the valve is opened
- Transfer of the remaining spray liquid to outside tank
{{tranfer_of_remaining_liquid.jpg}}
- Not available
- System for transfer of the remaining liquid available
Draining of diluted spray liquid
- Drain valve
==== Reference Standards ==== **ISO 4254-6** ==== Performance criteria ==== An emptying device in accordance with 4.5.3 of EN 907:1997 shall allow the complete emptying of the residual in the tank when the sprayer is in a horizontal position. Complete emptying of the residual is achieved if there are no visible puddles at the bottom of the tank after 5 min drainage.
- Not available
- Drain valve
{{simple_drain_valve.jpg}}
- Drain valve+sprinkling nozzle
EOS = Environmentally Optimised Sprayer
Evaluates technologies of Crop Protection sprayers on their risk mitigation capabilities to protect water and the environment
Top menu bar indicates relavant evaluation areas – click: if green it is active- Click on „problem“ menu bar below to open evaluation questionaire
- Technologies are listed in blue
- Click on one technical solution between each of the blue headlines (click on question marks to see an explaination (picture / comment)
- Go through the questionaire and complete all 5 areas indicated on top bar (after the completion of one area: click next button or next problem menu bar
- Technical solutions selected are compared with best available option by the EOS index (best is 100%). Results are shown by clicking on Evaluation results or in the buttons of the evaluation areas
- Results can be saved by clicking on save symbol: Enter a name and the E-Mail
Evaluation results
0 %
0 %
0 %
0 %
0 %
0 %